Electronic monitoring, conversion and display of input signals - all over the industries

Unsurpassed reliability, accuracy and long-term stability in critical processes. The remote configurable transmitter transfers and monitors converted signals from RTD sensors and thermocouples as well as from resistance and voltage signals using selectively HART®, FOUNDATION Fieldbus™-, PROFIBUS® PA-communication. It visualizes the signals on its own backlit display. A field housing allows a direct connection in harsh process areas as well as in hygienic applications as option.

  • Avantajlar

    • High reliability in harsh industrial environments due to dual compartment housing and compact, fully potted electronics

    • Backlit display with large measured value, bar graph and status condition indication

    • Diagnostics information according to NAMUR NE107

    • ...

  • Uygulama alanı

    • Universal input usable for resistance thermometer (RTD), thermocouple (TC), resistance thermometer (Ω), voltage transmitters (mV)

    • HART® protocol for converting various input signals to a scalable 4 to 20 mA analog output signal. Operating the...

Özellikler ve şartlar

Geri

Details

  • Measuring principle

    Resistance Temperature Detector

  • Input

    2 x RTD, TC, Ohm, mV

  • Output

    4...20 mA HART

    FOUNDATION Fieldbus H1

    PROFIBUS PA

  • Auxiliary power supply

    HART:

    11,5...42 V DC

    Ex ia: 11,5...30 V DC

    FOUNDATION Fieldbus:

    9...32 V DC

    Ex ia: 10,5...24 V DC

    PROFIBUS PA:

    9...32 V DC

    Ex ia: 10,5...24 V DC

  • Communication

    HART-protocol

    FOUNDATION Fieldbus

    PROFIBUS PA

  • Installation

    in field

  • Accuracy

    (Pt100, -50...200 °C) <= 0,15 K (HART)

    (Pt100, -58...392 °F) <= 0,3 °F (HART)

    (Pt100) <= 0,1 K (FF, PA)

    (Pt100) <= 0,18 °F (FF, PA)

  • Galvanic isolation

    yes

  • Certification

    UL rec. Comp (HART)

    FM IS, NI I/1+2/ABCD

    CSA IS, NI I/1+2/ABCD

    ATEX II1G Ex ia IIC T6

    ATEX II2G Ex d IIC T6

    ATEX II3G Ex nA IIC T6

    ATEX II3G Ex ic IIC T6

    ATEX IECEx II2D Ex tb IIIC Db

    ATEX II1G Ex ia IIC T6, II2D Ex ia IIIC

    FM XP, NI, DIP I,II,III/1+2/A-G

    CSA XP, NI, DIP I,II,III/1+2/A-G

    FM XP, DIP, IS, NI I,II,III/1+2/A-G

    CSA XP, DIP, IS, NI I,II,III/1+2/A-G

    FM+CSA XP,DIP, IS, NI I,II,III/1+2/A-G

    CSA General Purpose

    IECEx Ex d IIC T6 Gb

    IECEx Ex ia, Ex d

    NEPSI Ex ia IIC T4-T6

    NEPSI Ex nA II T4-T6

    NEPSI Ex d IIC T4-T6

    TIIS Ex ia IIC T4

    TIIS Ex ia IIC T6

    TIIS Ex d IIC T6

    Marine approval only for HART-protocol

    SIL2/3 only for HART-protocol

    EAC Ex ia IIC T6 Ga

    EAC Ex d IIC T6 Gb