Conductive
Point level detection
Pump Protection FTW360

Pump Protection FTW360 ©Endress+Hauser

Compact flush-mounted probe

The FTW360 is made for detection of liquids on the suction side of a pump for dry run protection. It operates in all conductive liquids, sludges and pastes that do not form an insulated build-up on the wall of the piping (e.g. oil film). The unit is also suitable for minimum or maximum detection in tanks.

  • Avantajlar

    • Simple and reliable solution also for adhesive or viscous products

    • Cost-effective probe for conductive liquids

    • Universal electronics for AC and DC voltages

  • Uygulama alanı

    For detection of liquids on the suction side of a pump for dry run protection. For conductive liquids, sludges and pastes that do not form an insulated build-up on the wall of the piping (e.g. oil film). For minimum or maximum detection in tanks.

    • ...

Özellikler ve şartlar

Geri

Details

  • Measuring principle

    Conductive

  • Characteristic / Application

    Compact limit switch for pump protection,
    Active build-up compensation,
    Flush mounting

  • Specialities

    CIP suiteable

  • Supply / Communication

    21V ... 253V AC
    20V ... 200V DC

  • Ambient temperature

    -20 °C ... 60 °C
    (-4 °F ... 140 °F)

  • Process temperature

    -20 °C ... 100 °C
    (-4 °F ... 212 °F)

  • Process pressure absolute / max. overpressure limit

    Vacuum ... 10 bar
    (Vacuum ... 145 psi)

  • Min. conductivity of medium

    10 µS/cm

  • Main wetted parts

    1.4571, PTFE

  • Process connection

    G3/4

  • Communication

    Relay

  • Application limits

    Observe minimum medium conductivity

Dokümanlar / Kılavuzlar / Yazılım

Aksesuarlar / Yedek parçalar

Nr
Order code
Specification
  • Önceki seri